Inductive loads don’t behave the same way that resistive loads do. To run an air conditioner (or any other electric motor) from a generator or inverter you need to oversize your generator. I don’t know the exact derating Factor you have to use, but two to three times is probably a good bet. So if your air conditioner needs 120 volts at 30 amps, that’s about 3.6 kw, so you want to make sure your generator is somewhere around 8 to 10 kilowatts to safely run that. In that case, your generator is almost certainly going to have the correct outlet.
If you don’t oversize your generator, you’re likely to cause damage to it from the surge current. Or it will continuously pop the breaker or cause the generator to stall.
Isn’t this going to be really loud? Your neighbors are going to hate you.
Yea I know it will be loud AF. This is a one time thing for this weekend only. I was told 3000 watts is what I need. I know the A/c is on a 20 amp breaker so I don’t actually need 30 amps but I’m worried the A/C with something else running might overload and pop the breaker on the Generator
Ryobi Inverter Generator – 3400W Run, 4000W Start This works great for my 30A RV, AC starts & runs just fine.