vballjudd:

It’s an issue with plug and socket. You stated you plugged a 30 Amp RV into that socket with a 15 Amp adapter. The adapter does NOT limit the current. It only adapts the plug to physically fit into the lower current socket. When you do that, it’s up to you to limit the current draw of the RV (never run the AC, limit simultaneous running of other high current items, etc.). I would replace the socket, and the adapter. You should also be sure to limit the draw of the camper in the future or install a proper 30 Amp circuit for the RV to avoid the fire risk in the future.

eastcoasternj:

The proximity of a faulty, burnt out receptacle to that gas tank is freaking me out man.

spchester:

It is possible that the 15 amp outlet has a 20 amp breaker. Therefore you would easily overload the outlet before tripping the breaker. If I was using something like that, long-term, I would probably invest in a 15 amp circuit breaker. Of course, the better option would be to install a 30 amp outlet.

Impossible_Treat5543:

That’s also a 15 amp receptacle so the wire feeding it is either 14 gauge or 12 gauge (15 and 20 amp respectively) it is a miracle that a little charring is all that happened.

Edit to add: your rv will draw the current it needs until the breaker for it trips, generally speaking a 15 amp breaker should hold up to about 12 amps, 20 amp breaker should hold 16 amps (you don’t want to exceed an 80% load). If you want to correctly run your rv power you’ll need 10/2 THHN to a single pole 30 amp breaker going to a 30 amp rv receptacle is what you need up to 50 ish feet then you should start using a heavier wire to accommodate your voltage drop.

Dr_Adequate:

It’s not about the plug or the adapter or the socket. What specific device was plugged in, and what was its current draw? Because that’s clear signs of overheating because whatever was plugged in was drawing a LOT of current.

ChonyJoe:

Loose connection. Probably faulty outlet. May have been the extra weight hanging from in all the time. Replace both the outlet and the plug.

MACCRACKIN:

Insert any plug into a sloppy 15amp outlet is about as smart as staring into the sun.

When a twenty amp out has ten times the grip.

But just look at that cooked outlet in the image here.
That’s obviously a slop loose outlet.

Everyone reading this should take a plug, go to every outlet in their home, with a fat red magic market, and if plug inserted can barely stay in with the slightest resistant pull, put a fat red mark across it, and start replacing them.

Every Fire Marshal should be thrown in a Rusian Gulag for signing off inspections they know are hazardous.

But they don’t care, they know stupid people will plug in a heater on the second and third floors with sloppy outlets knowing they’ll burn down with everyone inside sleeping. .

And Now You all Know the Truth @!
.
Cheers

Source: Question for electricians or those with electrical expertise. Had a 30amp plug with a 15amp adapter on this socket for about a year. Is this an issue with the plug or the socket?

How to Winterize Your RV eBook

FREE eBook...
'How to Winterize Your RV'

Your Guide for RV Winter Living & Storage.

Valuable Tips & Info help you prepare for cold weather. Includes winterization instructions for full-time or part-time winter RV living.

It's FREE and there's no obligation...
Download your copy today.

Thank You! You will be redirected to the eBook download page shortly... After you've had a read through, please let us know what you think about the 'How to Winterize Your RV' eBook.