There are (were) no near-floor level AC power outlets in my MH. Plugging in space heaters was awkward, the available plugs were kitchen counter or dining bench.
I’d removed my roof A/C after it stopped working (never run your roof A/C off of a 100ft 15 amp extension cable btw), so the dedicated 20 amp breaker in the power panel was free.
I left the A/C wiring in place, since I’d installed a duplex receptactle near where the A/C unit had been, and using 12/2 wiring rated for 20 amp circuits I tied in a new 15 amp duplex receptacle that I installed near the floor just under the power distribution.
So now I have 20 amps right near the floor, convenient for plugging in a heater.
I did a deep dive into the standards for 20 amp circuits, and yes, you can install 15 amp receptacles on a 20 amp circuit, as long as there are 2 or more and you use 12/2 throughout. And one duplex receptacle counts as two. And 15 amp receptacles have a 20 amp passthrough capacity.
If you noticed that I installed the receptacle ground pin up, it’s for a couple of reasons. In the part of the world I grew up that was the standard and I still instinctively orient plugs that way, and also it’s actually recommended: if a metallic object, say a coin or bit of wire, falls from above into a partially-out plug, it’s more likely to be in contact with ground before it shorts to hot or neutral, whereas in the traditional orientation a short between hot and neutral is almost certain. Or something like that.
The usual caveats apply. Electricity is dangerous and can cause fires. If you’re at all not sure of what you’re doing, find and/or pay someone competent to do it for you.
I thought a bit more about this, and you could do the same thing even if the A/C was still operational. Just don’t plug in any heavy-draw appliances when you’re using (in particular, starting) the A/C. (edit – not sure if that would be up to code)
Somehow this doesn’t add up.. 18 amps on a 15 amp receptacle are you forgetting about the 80% rule. 80% continuous load. Why didn’t you just spend the extra $1.50 and get the 20 amp plug I’m confused so now the 15 amp receptacle is the weakest link in the circuit. Hopefully it’s in a UL enclosure and not backstabbed.. oh I know receptacle ground is on the top so the heat from the two contacts can rise making the receptacle run cooler I get it now. It all makes sense. ???? My bad I apologize.